The Honeywell FC-TSDI-1624 is a high-reliability digital input module engineered for safety-critical applications within the Honeywell Safety Manager system. Designed to interface seamlessly between field sensors and the Fail-Safe Controller, this module ensures accurate signal transmission while maintaining the highest safety standards. It supports SIL 3 operation and is optimized for Emergency Shutdown (ESD), Fire and Gas (F&G), and hazardous process monitoring.
High-Integrity Input Channels
16 fully isolated digital input channels
Accepts 24 VDC nominal signals with a functional range of 18–30 VDC
Low input current (nominal 2–7 mA per channel) for efficient energy usage
Fast and Reliable Response
Signal processing time ≤ 25 ms
Ideal for applications requiring immediate feedback from critical field devices
Advanced Self-Diagnostics
Continuous internal testing verifies input logic and wiring integrity
Detects open circuits, shorts, and abnormal signal conditions
Front-panel LEDs provide visual indication for each channel and module status
Fail-Safe and Redundancy
Compatible with 1oo2 voting configurations for enhanced availability
Supports hot-swapping in redundant setups to minimize system downtime
Robust Industrial Design
IP65-rated enclosure for protection against dust and water ingress
Operating temperature: -40°C to +70°C (-40°F to 158°F)
Galvanic isolation prevents field-side surges from affecting system bus
Compact, space-saving design for high-density cabinet installation
| Feature | Specification |
|---|---|
| Module Type | Safe Digital Input (TSDI) |
| Channels | 16 |
| Nominal Voltage | 24 VDC |
| Voltage Range | 18–30 VDC |
| Input Current | 2–7 mA per channel |
| Input Low Threshold | < 5 VDC |
| Input High Threshold | > 15 VDC |
| Response Time | ≤ 25 ms |
| Safety Integrity | SIL 3 |
| Enclosure Rating | IP65 |
| Isolation | Galvanic between field and controller |
| Operating Temperature | -40°C to +70°C |
| Mounting | DIN rail or panel mount (FTA) |
The FC-TSDI-1624 is suited for critical safety loops including:
Emergency Shutdown Systems (ESD): Monitors safety interlocks and triggers process shutdowns.
Fire Alarm Systems: Interfaces with detectors to initiate alarms or suppression actions.
Gas Detection Systems: Continuously monitors gas levels and activates safety protocols when thresholds are exceeded.
Q: Can this module operate in SIL 3 rated loops?
A: Yes, individually SIL 3 certified and supports 1oo2 redundancy for higher availability.
Q: How are field wiring issues detected?
A: The module monitors open circuits, shorts, and cross-channel faults via internal diagnostics when paired with the correct Field Termination Assembly.
Q: Is hot-swapping supported?
A: Hot-swapping is possible in redundant configurations, allowing replacement without interrupting safety operation.
Q: What types of devices can be connected?
A: Push buttons, pressure switches, gas detectors, and other 24 VDC safety sensors.
Ships within 48 hours · Estimated delivery Jul 2 - Jul 7